Kalinsky

Pressure Transmitters  DS2-010 and DS2-420

applications:

control of airblowers

supervsion of airfilters

mechanical- and system engineering

environmental technology

liquid level control

description:

For applications with lower requirements on the temperature stability of the output-signal we offer alternative to DS1 the type DS2 as low cost pressure transmitter. The DS2 measures difference-pressure, positive and negative relative pressure or optionally velocity of flow. The analog output signal is 0-10 V or 4-20 mA.  Because of the piezoresistive cell the transmitter reach a high reliability and precision. They are housed in a robust aluminium package. This guarantees good EMV-properties.

An individual calibration certificate belongs to every pressure transmitter.

order key:

DS2-010 with 0-10 V output

DS2-420 with 4-20 mA output

technical data DS2-010 and DS2-420 (difference pressure):

pressure range [mbar]

pressure range [kPa]

max. over- pressure [mbar]

max.   linear error [ % F.S.]

max. temp. error
[ % F.S.]
0-50 C

long-term- stability              [ % F.S./ year]

repeat-preci sion  
[ % F.S.]

response time   [ms]

0 - 2.5

0 - 0.25

250

0.8

3.5

2

0.3

5

0 - 5

0 - 0.5

250

0.8

3

2

0.3

5

0 - 10

0 - 1

250

0.8

3

0.5

0.2

5

0 - 25

0 - 2.5

375

0.8

2.5

0.5

0.1

5

0 - 50

0 - 5

750

0.8

2.5

0.5

0.1

5

0 - 100

0 - 10

1125

0.8

2.5

0.5

0.1

5

For special ranges please enquire!

operation temperature range:

-20 bis +50 C

 

hysteresis:

0.1%

 

medium:

air and all non aggressive gases

output signals and power supply:

DS2-010:

0-10 V

RL>= 2 k

15-30 VDC

 

DS2-420:

4-20 mA

RB ... 20 up to 400

10-30 VDC

connections:

electrical:

screw clamps for 0.14 - 1.5 mm2

 

pneumatical:

2 connections for tube with 4 mm diameter inside

 

cable thread joint:

PG7

connection DS2- 010:

plug:

1 : + 24 VDC

 

 

2 : output 0 - 10 V

 

 

3 : GND

connection DS2- 420:

plug:

1 : + 24 VDC *

 

 

2 : output 4 - 20 mA *

* Because of a additional special circuit the transmitter canīt be damaged due to a wrong connection.

  That means:

both wires can be changed. Between 2 and GND of the power supply must be connected a resistor RB ... 20 up to 400 at power supply + 24 VDC.

optionally square root output (for measuring velocity of flow):

DS2 can measure the velocity of flow if it is completet with a square root output. Therefor a measuring blend or a Prandtl-tube must exist or be ordered.

weight:

approximately 170 g